High-voltage transformer fire barriers, also known as transformer firewalls, transformer ballistic firewalls, or transformer blast walls, are outdoor countermeasures against a fire or explosion involving a single transformer from damaging adjacent transformers. These barriers compartmentalizetransformer fires and explosions involving combustible transformer oil.
The primary North American document that deals with outdoor high-voltage transformer fire barriers is NFPA 850.[1] NFPA 850 outlines that outdoor oil-insulated transformers should be separated from adjacent structures and from each other by firewalls, spatial separation, or other approved means for the purpose of limiting the damage and potential spread of fire from a transformer failure.
Automatic fire suppression systems
Instead of a passive barrier, fire protection water spray systems are sometimes used to cool a transformer to prevent damage if exposed to radiation heat transfer from a fire involving oil released from another transformer that has failed.[2]
Transformer Fast Depressurization Systems (FDS)
Mechanical systems designed to quickly depressurize the transformer oil tank after the occurrence of an electrical fault [3] can minimize the chance that a transformer tank will rupture given a minor fault, but are not effective on major internal faults.[4]
Alternatives to mineral-based transformer oil
Transformer oil is available in with sufficiently low combustibility that a fire will not continue after an internal electrical fault. These fluids include those approved by FM Global.[5]FM Data Sheet 5-4 indicates different levels of protection depending on the type of fluid used. Alternatives include, but are not limited to, esters and silicone oil.[6]