A circuit breaker is an electrical safety device designed to protect an electrical circuit from damage caused by current in excess of that which the equipment can safely carry (overcurrent). Its basic function is to interrupt current flow to protect equipment and to prevent fire. Unlike a fuse, which operates once and then must be replaced, a circuit breaker can be reset (either manually or automatically) to resume normal operation.
Circuit breakers are commonly installed in distribution boards. Apart from its safety purpose, a circuit breaker is also often used as a main switch to manually disconnect ("rack out") and connect ("rack in") electrical power to a whole electrical sub-network.[1]
Circuit breakers are made in varying current ratings, from devices that protect low-current circuits or individual household appliances, to switchgear designed to protect high-voltage circuits feeding an entire city. Any device which protects against excessive current by automatically removing power from a faulty system, such as a circuit breaker or fuse, can be referred to as an over-current protection device (OCPD).
Origins
An early form of circuit breaker was described by Thomas Edison in an 1879 patent application, although his commercial power distribution system used fuses.[2] Its purpose was to protect lighting circuit wiring from accidental short circuits and overloads. A modern miniature circuit breaker similar to the ones now in use was patented by Brown, Boveri & Cie in 1924. Hugo Stotz, an engineer who had sold his company to Brown, Boveri & Cie, was credited as the inventor on German patent 458392.[3] Stotz's invention was the forerunner of the modern thermal-magnetic breaker commonly used in household load centers to this day.
Interconnection of multiple generator sources into an electrical grid required the development of circuit breakers with increasing voltage ratings and increased ability to safely interrupt the increasing short-circuit currents produced by networks. Simple air-break manual switches produced hazardous arcs when interrupting high-voltage circuits; these gave way to oil-enclosed contacts, and various forms using the directed flow of pressurized air, or pressurized oil, to cool and interrupt the arc. By 1935, the specially constructed circuit breakers used at the Boulder Dam project used eight series breaks and pressurized oil flow to interrupt faults of up to 2,500 MVA, in three AC cycles.[4]
Operation
All circuit breaker systems have common features in their operation, but details vary substantially depending on the voltage class, current rating and type of the circuit breaker.
The circuit breaker must first detect a fault condition. In small mains and low-voltage circuit breakers, this is usually done within the device itself. Typically, the heating or magnetic effects of electric current are employed. Circuit breakers for large currents or high voltages are usually arranged with protective relay pilot devices to sense a fault condition and to operate the opening mechanism. These typically require a separate power source, such as a battery, although some high-voltage circuit breakers are self-contained with current transformers, protective relays, and internal power sources.
Once a fault is detected, the circuit breaker contacts must open to interrupt the circuit; this is commonly done using mechanically stored energy contained within the breaker, such as a spring or compressed air to separate the contacts. A breaker may also use the higher current caused by the fault to separate the contacts, via thermal expansion or increased magnetic field. A small circuit breaker typically has a manual control lever to switch the circuit off or reset a tripped breaker, while a larger unit may use a solenoid to trip the mechanism, and an electric motor to restore energy to springs (which rapidly separate contacts when the breaker is tripped).
The circuit breaker contacts must carry the load current without excessive heating, and must also withstand the heat of the arc produced when interrupting (opening) the circuit. Contacts are made of copper or copper alloys, silver alloys and other highly conductive materials. Service life of the contacts is limited by the erosion of contact material due to arcing while interrupting the current. Miniature and molded-case circuit breakers are usually discarded when the contacts have worn, but power circuit breakers and high-voltage circuit breakers have replaceable contacts.
When a high current or voltage is interrupted, an arc is generated. The maximum length of the arc is generally proportional to the voltage while the intensity (or heat) is proportional to the current. This arc must be contained, cooled and extinguished in a controlled way, so that the gap between the contacts can again withstand the voltage in the circuit. Different circuit breakers use vacuum, air, insulating gas, or oil as the medium the arc forms in. Different techniques are used to extinguish the arc including:
Lengthening or deflecting the arc
Intensive cooling (in jet chambers)
Division into partial arcs
Zero-point quenching (contacts open at the moment in the AC waveform at which the current and potential are near zero, effectively breaking no load current at the time of opening. The zero-crossing occurs at twice the line frequency; i.e., 100 times per second for 50 Hz and 120 times per second for 60 Hz AC.)
Connecting capacitors in parallel with contacts in DC circuits.
Finally, once the fault condition has been cleared, the contacts must again be closed to restore power to the interrupted circuit.
Arc interruption
Low-voltage miniature circuit breakers (MCB) use air alone to extinguish the arc. These circuit breakers contain so-called arc chutes, a stack of mutually insulated parallel metal plates that divide and cool the arc. By splitting the arc into smaller arcs the arc is cooled down while the arc voltage is increased and serves as an additional impedance that limits the current through the circuit breaker. The current-carrying parts near the contacts provide easy deflection of the arc into the arc chutes by a magnetic force of a current path, although magnetic blowout coils or permanent magnets could also deflect the arc into the arc chute (used on circuit breakers for higher ratings). The number of plates in the arc chute is dependent on the short-circuit rating and nominal voltage of the circuit breaker.
In larger ratings, oil circuit breakers rely upon vaporization of some of the oil to blast a jet of oil through the arc.[5]
Gas (usually sulfur hexafluoride) circuit breakers sometimes stretch the arc using a magnetic field, and then rely upon the dielectric strength of the sulfur hexafluoride (SF6) to quench the stretched arc.
Vacuum circuit breakers have minimal arcing (as there is nothing to ionize other than the contact material). The arc is quenched when it is stretched a very small amount (less than 3 mm (0.1 in)). Vacuum circuit breakers are frequently used in modern medium-voltage switch gear to 38000 volts.
Air circuit breakers may use compressed air to blow out the arc, or alternatively, the contacts are rapidly swung into a small sealed chamber, the escaping of the displaced air thus blowing out the arc.
Circuit breakers are usually able to terminate all current very quickly: typically the arc is extinguished between 30 and 150 ms after the mechanism has been tripped, depending upon age and construction of the device. The maximum current value and let-through energy determine the quality of the circuit breakers.
Short circuit
Circuit breakers are rated both by the normal current that they are expected to carry, and the maximum short-circuit current that they can safely interrupt. This latter figure is the ampere interrupting capacity (AIC) of the breaker.
Under short-circuit conditions, the calculated or measured maximum prospective short-circuit current may be many times the normal, rated current of the circuit. When electrical contacts open to interrupt a large current, there is a tendency for an arc to form between the opened contacts, which would allow the current to continue. This condition can create conductive ionized gases and molten or vaporized metal, which can cause the further continuation of the arc or create additional short circuits, potentially resulting in the explosion of the circuit breaker and the equipment that it is installed in. Therefore, circuit breakers incorporate various features to divide and extinguish the arcs.
The maximum short-circuit current that a breaker can interrupt is determined by testing. Application of a breaker in a circuit with a prospective short-circuit current higher than the breaker's interrupting capacity rating may result in failure of the breaker to safely interrupt a fault. In a worst-case scenario, a breaker may successfully interrupt a fault only to explode when reset.
Typical domestic panel circuit breakers are rated to interrupt 6 kA (6000 A) short-circuit current.
Miniature circuit breakers used to protect control circuits or small appliances may not have sufficient interrupting capacity to use at a panel board; these circuit breakers are called "supplemental circuit protectors" to distinguish them from distribution-type circuit breakers.
Standard current ratings
Circuit breakers are manufactured with standard ratings, using a system of preferred numbers to create a useful selection of ratings. A miniature circuit breaker has a fixed trip setting; changing the operating current value requires replacing the whole circuit breaker. Circuit breakers with higher ratings can have adjustable trip settings, allowing fewer standardized products to be used, adjusted to the applicable precise ratings when installed. For example, a circuit breaker with a 400 ampere frame size might have its over-current detection threshold set only 300 amperes where that rating is appropriate.
For low-voltage distribution circuit breakers an international standard, IEC 60898-1, defines rated current as the maximum current that a breaker is designed to carry continuously. The commonly available preferred values for rated current are 1A, 2A, 4A, 6 A, 10 A, 13 A, 16 A, 20 A, 25 A, 32 A, 40 A, 50 A, 63 A, 80 A, 100 A,[6] and 125 A. The circuit breaker is labeled with the rated current in amperes prefixed by a letter, which indicates the instantaneous tripping current that causes the circuit breaker to trip without intentional time delay expressed in multiples of the rated current:
Type
Instantaneous tripping current
B
3–5 times rated current In, e.g. a nominally 10 A device will trip at 30–50 A
C
5–10 times In
D
10–14 times In
K
8–12 times In
For the protection of loads that cause frequent short-duration (approximately 400 ms to 2 s) current peaks in normal operation
Z
2–3 times In for durations on the order of tens of seconds.
For the protection of loads such as semiconductor devices or measuring circuits using current transformers.
Circuit breakers are also rated by the maximum fault current that they can interrupt; this allows use of more economical devices on systems unlikely to develop the high short-circuit current found on, for example, a large commercial building distribution system.
In the United States, Underwriters Laboratories (UL) certifies equipment ratings, called Series Ratings (or "integrated equipment ratings") for circuit breaker equipment used for buildings. Power circuit breakers and medium- and high-voltage circuit breakers used for industrial or electric power systems are designed and tested to ANSI or IEEE standards in the C37 series. For example, standard C37.16 lists preferred frame size current ratings for power circuit breakers in the range of 600 to 5000 amperes. Trip current settings and time–current characteristics of these breakers are generally adjustable.
For medium- and high-voltage circuit breakers used in switchgear, substations and generating stations, relatively few standard frame sizes are generally manufactured. These circuit breakers are usually controlled by separate protective relay systems, offering adjustable tripping current and time settings as well as allowing for more complex protection schemes.
Types
Many classifications of circuit breakers can be made, based on their features such as voltage class, construction type, interrupting type, and structural features.
Low-voltage
Low-voltage (less than 1,000 VAC) types are common in domestic, commercial and industrial application, and include:
Miniature circuit breaker (MCB)—rated current up to 125 A. Trip characteristics normally not adjustable. Thermal or thermal-magnetic operation. Breakers illustrated above are in this category.
Molded Case Circuit Breaker (MCCB)—rated current up to 1,600 A. Thermal or thermal-magnetic operation. Trip current may be adjustable in higher-rated units.
Low-voltage power circuit breakers can be mounted in multiple tiers in low-voltage switchboards or switchgear cabinets.
The characteristics of low-voltage circuit breakers are given by international standards such as IEC 947. These circuit breakers are often installed in draw-out enclosures that allow removal and interchange without dismantling the switchgear.
Large low-voltage molded-case and power circuit breakers may have electric motor operators so they can open and close under remote control. These may form part of an automatic transfer switch system for standby power.
Low-voltage circuit breakers are also made for direct-current (DC) applications, such as for subway lines. Direct current requires special breakers because the arc is continuous—unlike an AC arc, which tends to go out on each half cycle, a direct-current circuit breaker has a blow-out coil that generates a magnetic field that rapidly stretches the arc. Small circuit breakers are either installed directly in equipment or arranged in breaker panels.
The DIN-rail-mounted thermal-magnetic miniature circuit breaker is the most common style in modern domestic consumer units and commercial electrical distribution boards throughout Europe. The design includes the following components:
Actuator lever – used to manually trip and reset the circuit breaker. Also indicates the status of the circuit breaker (On or Off/tripped). Most breakers are designed so they can still trip even if the lever is held or locked in the "on" position. This is sometimes referred to as "free trip" or "positive trip" operation.
Actuator mechanism – forces the contacts together or apart.
Contacts – allow current when touching and break the current when moved apart.
Terminals
Bimetallic strip – separates contacts in response to smaller, longer-term overcurrents
Calibration screw – allows the manufacturer to precisely adjust the trip current of the device after assembly.
Solenoid – separates contacts rapidly in response to high overcurrents
Arc divider/extinguisher
Solid-state
Solid-state circuit breakers (SSCBs), also known as digital circuit breakers, are a technological innovation which promises to advance circuit breaker technology out of the mechanical level, into the electrical. This promises several advantages, such as acting much more quickly (breaking circuits in fractions of microseconds), better monitoring of circuit loads and longer lifetimes.[7] Solid-state circuit breakers have been developed for medium-voltage DC power and can use silicon carbide transistors or integrated gate-commutated thyristors (IGCTs) for switching.[8][9][10]
Magnetic
A magnetic circuit breaker uses a solenoid (electromagnet) whose pulling force increases with the current. Certain designs utilize electromagnetic forces in addition to those of the solenoid. The circuit breaker contacts are held closed by a latch. As the current in the solenoid increases beyond the rating of the circuit breaker, the solenoid's pull releases the latch, which lets the contacts open by spring action. They are the most commonly used circuit breakers in the United States.
Thermal–magnetic
A thermal–magnetic circuit breaker, which is the type found in most distribution boards in Europe and countries with a similar wiring arrangement, incorporates both techniques with the electromagnet responding instantaneously to large surges in current (such as short circuits) and the bimetallic strip responding to lesser but longer-term over-current conditions. The thermal portion of the circuit breaker provides a time-response feature that trips the circuit breaker sooner for larger over-currents but allows smaller overloads to persist for a longer time. This allows short current spikes such as are produced when a motor or other non-resistive load is switched on. With a very large over-current, such as may be caused short circuit, the magnetic element trips the circuit breaker with no intentional additional delay.[11]
Magnetic–hydraulic
A magnetic–hydraulic circuit breaker uses a solenoid coil to provide operating force to open the contacts. A magnetic–hydraulic breaker incorporates a hydraulic time delay feature using a viscous fluid. A spring restrains the core until the current exceeds the breaker rating. During an overload, the speed of the solenoid motion is restricted by the fluid. The delay permits brief current surges beyond normal running current for motor starting, energizing equipment, etc. Short-circuit currents provide sufficient solenoid force to release the latch regardless of core position thus bypassing the delay feature. Ambient temperature affects the time delay but does not affect the current rating of a magnetic breaker.[12]
A large power circuit breaker, such as one applied in circuits of more than 1000 volts, may incorporate hydraulic elements in the contact operating mechanism. Hydraulic energy may be supplied by a pump or stored in accumulators. These form a distinct type from oil-filled circuit breakers where oil is the arc-extinguishing medium.[13]
Common-trip (ganged) breakers
To provide simultaneous breaking on multiple circuits from a fault on any one, circuit breakers may be made as a ganged assembly. This is a very common requirement for three-phase systems, where breaking may be either three- or four-pole (solid or switched neutral). Some makers make ganging kits to allow groups of single-phase breakers to be interlinked as required.
In the US, where split-phase supplies are common, in a branch circuit with more than one live conductor, each live conductor must be protected by a breaker pole. To ensure that all live conductors are interrupted when any pole trips, a common-trip set of breakers must be used. These may either contain two or three tripping mechanisms within one case or, for small breakers, have the breakers externally tied together via their operating handles. Two-pole common-trip breakers are common on 120/240-volt systems where 240 volt loads (including major appliances or further distribution boards) span the two live wires. Three-pole common-trip breakers are typically used to supply three-phase power to powerful motors or further distribution boards.
Separate circuit breakers must never be used for live and neutral, because if the neutral is disconnected while the live conductor stays connected, a very dangerous condition arises: the circuit appears de-energized (appliances don't work), but wires remain live and some residual-current devices (RCDs) may not trip if someone touches the live wire (because some RCDs need power to trip). This is why only common-trip breakers must be used when neutral wire switching is needed.
Shunt-trip units
A shunt-trip unit appears similar to a normal breaker and the moving actuators are ganged to a normal breaker mechanism to operate together in a similar way, but the shunt trip is a solenoid intended to be operated by an external constant-voltage signal, rather than a current, commonly the local mains voltage or DC. These are often used to cut the power when a high-risk event occurs, such as a fire or flood alarm, or another electrical condition, such as over-voltage detection. Shunt trips may be a user-fitted accessory to a standard breaker or supplied as an integral part of a circuit breaker.
Medium-voltage
Medium-voltage circuit breakers rated between 1 and 72kV may be assembled into metal-enclosed switchgear line-ups for indoor use or may be individual components installed outdoors in a substation. Air-break circuit breakers replaced oil-filled units for indoor applications, but are now themselves being replaced by vacuum circuit breakers (up to about 40.5kV). Like the high-voltage circuit breakers described below, these are also operated by current-sensing protective relays operated through current transformers. The characteristics of MV breakers are given by international standards such as IEC 62271. Medium-voltage circuit breakers nearly always use separate current sensors and protective relays instead of relying on built-in thermal or magnetic overcurrent sensors.
Medium-voltage circuit breakers can be classified by the medium used to extinguish the arc:
Vacuum circuit breakers—With rated current up to 6,300A, and higher for generator circuit breakers application (up to 16,000A & 140kA). These breakers interrupt the current by creating and extinguishing the arc in a vacuum container – aka "bottle". Long life bellows are designed to travel the 6–10 mm the contacts must part. These are generally applied for voltages up to about 40,500V,[14] which corresponds roughly to the medium-voltage range of power systems. Vacuum circuit breakers have longer life expectancy between overhaul than do other circuit breakers. In addition their global warming potential is by far lower than SF6 circuit breaker.
Air circuit breakers—Rated current up to 6,300A and higher for generator circuit breakers. Trip characteristics are often fully adjustable including configurable trip thresholds and delays. Usually electronically controlled, though some models are microprocessor controlled via an integral electronic trip unit. Often used for main power distribution in large industrial plant, where the breakers are arranged in draw-out enclosures for ease of maintenance.
Medium-voltage circuit breakers may be connected into the circuit by bolted connections to bus bars or wires, especially in outdoor switchyards. Medium-voltage circuit breakers in switchgear line-ups are often built with draw-out construction, allowing breaker removal without disturbing power circuit connections, using a motor-operated or hand-cranked mechanism to separate the breaker from its enclosure.
Electrical power transmission networks are protected and controlled by high-voltage breakers. The definition of high voltage varies but in power transmission work is usually thought to be 72.5 kV or higher, according to a recent definition by the International Electrotechnical Commission (IEC). High-voltage breakers are nearly always solenoid-operated, with current sensing protective relays operated through current transformers. In substations the protective relay scheme can be complex, protecting equipment and buses from various types of overload or ground/earth fault.
High-voltage breakers are broadly classified by the medium used to extinguish the arc:
Due to environmental and cost concerns over insulating oil spills, most new breakers use SF6 gas to quench the arc.
Circuit breakers can be classified as live tank, where the enclosure that contains the breaking mechanism is at line potential, or dead tank with the enclosure at earth potential. High-voltage AC circuit breakers are routinely available with ratings up to 765 kV. 1,200kV breakers were launched by Siemens in November 2011,[15] followed by ABB in April the following year.[16]
High-voltage circuit breakers used on transmission systems may be arranged to allow a single pole of a three-phase line to trip, instead of tripping all three poles; for some classes of faults this improves the system stability and availability.
High-voltage direct current circuit breakers are still a field of research as of 2015. Such breakers would be useful to interconnect HVDC transmission systems.[17]
A sulfur hexafluoride circuit breaker uses contacts surrounded by sulfur hexafluoride gas to quench the arc. They are most often used for transmission-level voltages and may be incorporated into compact gas-insulated switchgear. In cold climates, supplemental heating or different gas mixtures are used for high voltage circuit breakers, due to liquefaction of the SF6 gas. In some northern power grids, gas mixtures of N2 and SF6, or CF4 and SF6 are installed in puffer-type HVCB to quench the arc without any liquefaction of the gas. https://ieeexplore.ieee.org/abstract/document/4080767. The minimum temperature ratings of these models are as low as -50 °C for some northern substations.
Disconnecting circuit breaker (DCB)
The disconnecting circuit breaker (DCB) was introduced in 2000[18] and is a high-voltage circuit breaker modeled after the SF6-breaker. It presents a technical solution where the disconnecting function is integrated in the breaking chamber, eliminating the need for separate disconnectors. This increases the availability, since open-air disconnecting switch main contacts need maintenance every 2–6 years, while modern circuit breakers have maintenance intervals of 15 years. Implementing a DCB solution also reduces the space requirements within the substation, and increases the reliability, due to the lack of separate disconnectors.[19][20]
In order to further reduce the required space of substation, as well as simplifying the design and engineering of the substation, a fiber optic current sensor (FOCS) can be integrated with the DCB. A 420 kV DCB with integrated FOCS can reduce a substation's footprint with over 50% compared to a conventional solution of live tank breakers with disconnectors and current transformers, due to reduced material and no additional insulation medium.[21]
Carbon dioxide (CO2) high-voltage
In 2012, ABB presented a 75kV high-voltage breaker that uses carbon dioxide as the medium to extinguish the arc. The carbon dioxide breaker works on the same principles as an SF6 breaker and can also be produced as a disconnecting circuit breaker. By switching from SF6 to CO2, it is possible to reduce the CO2 emissions by 10 tons during the product's life cycle.[22]
"Smart" circuit breakers
Several firms have looked at adding monitoring for appliances via electronics or using a digital circuit breaker to monitor the breakers remotely. Utility companies in the United States have been reviewing use of the technology to turn appliances on and off, as well as potentially turning off charging of electric cars during periods of high electrical grid load. These devices under research and testing would have wireless capability to monitor the electrical usage in a house via a smartphone app or other means.[23]
Other breakers
The following types are described in separate articles.
Breakers for protections against earth faults too small to trip an over-current device:
Residual-current device (RCD), or residual-current circuit breaker (RCCB) — detects current imbalance, but does not provide over-current protection. In the United States and Canada, these are called ground fault circuit interrupters (GFCI).
Residual-current circuit breaker with overcurrent protection (RCBO) — combines the functions of a RCD and a MCB in one package. In the United States and Canada, these are called GFCI breakers.
Earth leakage circuit breaker (ELCB) — This detects current in the earth wire directly rather than detecting imbalance. They are no longer seen in new installations as they cannot detect any dangerous condition where the current is returning to earth by another route – such as via a person on the ground or via plumbing. (also called VOELCB in the UK).
Arc-fault circuit interrupter (AFCI) or arc-fault detection device (AFDD) — detects electric arcs from the likes of loose wires.
Recloser — A type of circuit breaker that closes automatically after a delay. These are used on overhead electric power distribution systems, to prevent short duration faults from causing sustained outages.
Polyswitch (polyfuse) — A small device commonly described as an automatically resetting fuse rather than a circuit breaker.
^Robert Friedel and Paul Israel, Edison's Electric Light: Biography of an Invention, Rutgers University Press, New Brunswick New Jersey USA,1986 ISBN0-8135-1118-6 pp.65-66
BS EN 60898-1. Electrical accessories — Circuit breakers for over-current protection for household and similar installations. British Standards Institution, 2003.
Pigmentasi kulit beralih ke halaman ini. Untuk pigmentasi kulit hewan, lihat Pigmen biologis. Keluarga besar Coloured dari Afrika Selatan menampilkan beberapa spektrum pewarnaan kulit manusia Pigmen warna kulit manusia memiliki keragaman dari coklat tergelap sampai putih terterang. Pigmentasi kulit seseorang adalah hasil dari genetik, produk dari kedua orangtua biologis seseorang, riasan genetik dan pancaran sinar matahari. Dalam evolusi, pigmentasi kulit pada manusia berubah akibat proses se...
Див. також: Вікторіно У Вікіпедії є статті про інших людей із прізвищем Пласа. Вікторіно де ла Пласа ісп. Victorino de la Plaza Вікторіно де ла ПласаПрезидент Аргентини 9 серпня 1914 — 12 жовтня 1916Попередник Роке Саенс ПеньяНаступник Іполіто ІріґоєнВіцепрезидент Аргентини 12 жовт
Die Liste der Kulturdenkmale in Gompitz umfasst sämtliche Kulturdenkmale der Dresdner Gemarkung Gompitz. Grundlage bildet das Denkmalverzeichnis des Themenstadtplans Dresden, das sämtliche bis Januar 2006 vom Landesamt für Denkmalpflege Sachsen erfassten Kulturdenkmale beinhaltet. Legende Bild: Bild des Kulturdenkmals, ggf. zusätzlich mit einem Link zu weiteren Fotos des Kulturdenkmals im Medienarchiv Wikimedia Commons Bezeichnung: Denkmalgeschützte Objekte und ggf. Bauwerksname des Kult...
Alat pengatur siklus suhu yang biasanya digunakan pada teknik reaksi berantai polimeraseReaksi berantai polimerase (bahasa Inggris: polymerase chain reaction, disingkat PCR) adalah metode untuk menciptakan jutaan hingga miliaran salinan dari segmen asam deoksiribonukleat (DNA) tertentu, yang memungkinkan ilmuwan untuk melipatgandakan sampel DNA yang sangat sedikit hingga mencapai jumlah yang cukup untuk dipelajari secara detail. Metode ini ditemukan pada tahun 1983 oleh Kary Mullis, ahli biok...
Castillo de Castrogeriz Munio Núñez, Comte Kastila (899–skt. 901 and skt. 904–skt. 909),[1] adalah seorang bangsawan yang hampir pasti adalah putra Nuño Muñoz, putra Munio Núñez de Brañosera yang pada 824, dengan istrinya Argilo, mengabulkan Carta Puebla de Brañosera,[2][3] Fuero mirip dengan custumal Inggris abad pertengahan yang menetapkan adat dan peraturan ekonomi, politik, dan sosial untuk mengatur kota, dalam hal ini, Brañosera yang baru saja dihuni ...
Utah negara bagian di Amerika Serikat State of Utah (en) flag of Utah (en) Lagu kebangsaanUtah, This Is the Place (en) (2003) Moto«Industry» Lambang resmiRocky Mountain elk (en) , California Gull (en) , Basi (alat masak), Sarang lebah, Bonneville cutthroat trout (en) , Calochortus nuttallii (en) , square dance (en) , Allosaurus, Ceri, Topaz, Achnatherum hymenoides (en) , Apis, tembaga, batu bara, Utah, This Is the Place (en) , Utah, We Love Thee (en) , Alpha Ursae Majoris (en) , Populus tre...
Slovenian poet (1941–2014) Tomaž ŠalamunŠalamun in 2005Born(1941-07-04)July 4, 1941Zagreb, Independent State of CroatiaDiedDecember 27, 2014(2014-12-27) (aged 73)Ljubljana, SloveniaOccupationPoetLanguageSloveneNationalitySlovenianAlma materUniversity of LjubljanaLiterary movementNeo-avant-gardeNotable awardsPushcart Prize, Prešeren Fund Award, European Prize for PoetrySpouseMetka Krašovec Tomaž Šalamun (July 4, 1941 – December 27, 2014) was a Slovenian poet who was a lead...
District Municipality in Aukštaitija, LithuaniaJoniškis District Municipality Joniškio rajono savivaldybėDistrict MunicipalityMorning in Mūša Upland Bog Coat of armsLocation of Joniškis District Municipality within LithuaniaLocation of JoniškisCoordinates: 56°14′28″N 23°36′55″E / 56.24111°N 23.61528°E / 56.24111; 23.61528Country LithuaniaRegionAukštaitijaCountyŠiauliai CountyEstablished1950 (73 years ago) (1950)CapitalJoniškisE...
Not to be confused with Shenzhen Bay Port, a port of entry on the border with Hong Kong. Port in People's Republic of ChinaPort of Shenzhen 深圳港LocationCountry People's Republic of ChinaLocationShenzhen, GuangdongDetailsOwned byShenzhen Government Port of ShenzhenSimplified Chinese深圳港Traditional Chinese深圳港TranscriptionsStandard MandarinHanyu PinyinShēnzhèn GǎngWade–GilesShen-chen kangYue: CantoneseYale RomanizationSāmJan GóngJyutpingSam1zan3 Gong2 The P...
Bridge over the River Liffey in Ireland Millennium BridgeDroichead na MílaoiseCoordinates53°20′46″N 6°15′54″W / 53.346°N 6.265°W / 53.346; -6.265CarriesPedestriansCrossesRiver LiffeyLocaleDublin, IrelandCharacteristicsMaterialSteel and concrete[1]Total length51 m (41 m span)[1]Width~4mNo. of spans1HistoryDesignerHowley Harrington (architects), Price & Myers (engineers)Constructed byAscon (contractor), Thompson Engineering (steel structu...
Australian newspaper The Toowoomba ChronicleTypeDaily newspaperFormatTabloidOwner(s)News Corp AustraliaEditorSteve EtwellNews editorWill HunterFounded1922LanguageEnglishHeadquartersToowoomba, Queensland, AustraliaLevel 1/5 Keefe StToowoomba QLD 4350Circulation22,808 Monday-Friday30,270 SaturdayWebsitethechronicle.com.au The Toowoomba Chronicle is a daily newspaper serving Toowoomba, the Lockyer Valley and Darling Downs regional areas in Queensland, Australia. As of 2016, the newspaper is owne...
American car model Motor vehicle Oldsmobile Cutlass1971 Oldsmobile Cutlass Supreme ConvertibleOverviewManufacturerOldsmobile (General Motors)Production1961–1999Body and chassisClassCompact (1961–1963)Mid-size (1964–1981, 1997–1999)Personal luxury car (1968–1988)ChronologySuccessorOldsmobile Intrigue The Oldsmobile Cutlass was a series[1] of automobiles produced by General Motors' Oldsmobile division between 1961 and 1999. At its introduction, the Cutlass was Oldsmobile's ent...
Office building in Manhattan, New York 65 BroadwayFormer namesRailway Express Company Building, American Express Building, J.J. Kenny Company BuildingAlternative namesStandard & Poors BuildingGeneral informationTypeOfficeArchitectural styleNeoclassicalAddress63-65 BroadwayTown or cityFinancial District, Manhattan, New YorkCountryUnited StatesCoordinates40°42′26″N 74°00′45″W / 40.70722°N 74.01250°W / 40.70722; -74.01250Construction started1916Completed19...
This article does not cite any sources. Please help improve this article by adding citations to reliable sources. Unsourced material may be challenged and removed.Find sources: Centre sportif Léonard-Grondin – news · newspapers · books · scholar · JSTOR (May 2009) (Learn how and when to remove this template message) The Centre sportif Léonard-Grondin after the 2010-2011 renovations The Centre sportif Léonard-Grondin (historically known as the Aréna...
Inside the Electric CircusÁlbum de W.A.S.P.Publicación Noviembre de 1986Grabación Pasha Music House, North Hollywood, Los Ángeles, CaliforniaGénero(s) Heavy metal, hard rockDuración 47:14Discográfica CapitolProductor(es) Blackie LawlessCalificaciones profesionales Allmusic enlace Cronología de W.A.S.P. The Last Command(1985) Inside the Electric Circus Live... in the Raw(1987) [editar datos en Wikidata] Inside the Electric Circus es el tercer álbum de la banda de heavy metal...
التطليق لحبس الزوج في القانون المصري تطلبه الزوجة المصرية المسلمة من القضاء إذا صدر ضد زوجها حكماً نهائياً بعقوبة مقيدة للحرية لا تقل مدتها عن 3 سنوات، بما يشمل السجن المشدد والمؤبد، وذلك بعد مرور سنة على حبسه، وليس عليها إثبات الضرر الذي يكون مفترضاً في تلك الحالة. والتطل...
Irish footballer (1923–2004) Tommy Eglington Eglington c. 1959Personal informationFull name Thomas Joseph EglingtonDate of birth (1923-01-15)15 January 1923Place of birth Donnycarney, County Dublin, IrelandDate of death 18 February 2004(2004-02-18) (aged 81)Place of death Raheny, County Dublin, IrelandPosition(s) Outside-leftYouth career Munster Victoria1942 Distillery (Dublin)Senior career*Years Team Apps (Gls)1942–1946 Shamrock Rovers ? (17)1946–1957 Everton 394 (76)1957–1961 T...
«Gerardo Romano» redirige aquí. Para el pelotari Gerardo Gabriel Romano, véase Gerardo Romano (pelotari). Gerardo Romano Gerardo Romano en 2021.Información personalNombre de nacimiento Luis Gerardo RomanoNacimiento 6 de julio de 1946 (77 años)Buenos Aires, ArgentinaNacionalidad ArgentinaReligión AteoFamiliaPareja Leonor BenedettoAndrea Bonelli (1988 - 1991)Hijos Lucio Romano Bonelli Rita RomanoEducaciónEducado en Universidad de Buenos Aires Información profesionalOcupació...
Kolonia Chełmska kolonia Państwo Polska Województwo małopolskie Powiat olkuski Gmina Wolbrom Strefa numeracyjna 32 Kod pocztowy 32-340[2] Tablice rejestracyjne KOL SIMC 0224018 Położenie na mapie gminy WolbromKolonia Chełmska Położenie na mapie PolskiKolonia Chełmska Położenie na mapie województwa małopolskiegoKolonia Chełmska Położenie na mapie powiatu olkuskiegoKolonia Chełmska 50°21′26″N 19°43′49″E/50,357222 19,730278[1] Kolonia Chełmska ...